The Vulcan-Hp chill pumps are mainly used in a Marine Farming Plants & industrial manufacturing facilities.
The pump removes the latent heat from the water transferring it to the surrounding atmosphere.
This means that 80% of the cooling requirements are obtained from nature and there is only
the need for 20% of electrial input making these pumps the most reliable and efficient way of cooling water.
Electronic control panel: automatically allows you to achieve optimum performance throughout the full range of operating conditions, making the Vulcan-HP® swimming pool heat/chill pump the most efficient pool heater/chiller available. The control panel features a digital display, programmable thermostat and control indicator lights.
Condenser air coil: extra large, designed to maximise latent heat transfer.
Outer casing: made of 304 stainless steel, stylish and durable.
Fan motor: high performance, that allows for maximum efficiency and quiet operation.
Heat exchanger: pure titanium tubing in stainless steel 316 casing, to optimise heat transfer.
Compressor: Copeland Compliant Scroll, the most efficient, reliable and quietest in the range.
Refrigerant: Standard: R22 (HCFC),
Optional: R407C
Water connections: 50mm Coupled Unions.
| Chill pumps |
V20C |
V25C |
V30C |
V40C |
V50C |
V60C |
V80C |
V100C |
V120C |
V160C |
| Compressor |
Suction Gas Cooled Compressors |
| Refrigerant |
R22 |
R22 |
R22 |
R22 |
R22 |
R22 |
R22 |
R22 |
R22 |
R22 |
| Voltage |
380/420V |
380/420V |
380/420V |
380/420V |
380/420V |
380/420V |
380/420V |
380/420V |
380/420V |
380/420V |
| Phase |
3Ph |
3Ph |
3Ph |
3Ph |
3Ph |
3Ph |
3Ph |
3Ph |
3Ph |
3Ph |
| Frequency |
50hz |
50hz |
50hz |
50hz |
50hz |
50hz |
50hz |
50hz |
50hz |
50hz |
| Max. Operating current |
10A |
10A |
11A |
16A |
18A |
19A |
32A |
36A |
38A |
55A |
| Locked Rotor Current |
50A |
66A |
74A |
101A |
123A |
127A |
202A |
246A |
254A |
396A |
| Sound pressure @ 1 m |
57dB |
59dB |
60dB |
61dB |
65dB |
65dB |
61dB |
65dB |
65dB |
75dB |
| Max. High Pressure |
27.5 bar |
27.5 bar |
27.5 bar |
27.5 bar |
32 bar |
28 bar |
27.5 bar |
32 bar |
32 bar |
32 bar |
| Max. Standstill pressure |
17 bar |
17 bar |
17 bar |
27 bar |
20 bar |
17 bar |
17 bar |
20 bar |
20 bar |
22 bar |
| Nominal water flow |
120/150 l/min |
120/150 l/min |
120/150 l/min |
180/200 l/min |
180/200 l/min |
180/200 l/min |
180/200 l/min |
200/220 l/min |
200/220 l/min |
200/220 l/min |
| Nominal air flow x1000 |
6m3/h |
7m3/h |
7m3/h |
11m3/h |
12m3/h |
12m3/h |
22m3/h |
24m3/h |
24m3/h |
24m3/h |
|
Nominal cooling capacity
|
| Cooling duty |
14.61kW |
16.94kW |
20.05kW |
24.24kW |
30.77kW |
37.29kW |
48.48kW |
61.54kW |
74,58kW |
121kW |
| Power input |
3.32kW |
4.22kW |
4.81kW |
5.38kW |
7.21kW |
8.28kW |
10.76kW |
14.42kW |
16.56kW |
24.8kW |
| C.O.P. |
4.40 |
4.01 |
4.27 |
4.5 |
4.26 |
4.50 |
4.50 |
4.26 |
4.50 |
4.89 |
| Running current @ 400V |
6.04A |
16.94A |
8.56A |
10.34A |
13.47A |
15.47A |
20.68A |
26.94A |
30.94A |
22.1A |
|
Dimensions
|
| Length (mm) |
960 |
960 |
1060 |
1060 |
1040 |
1040 |
1020 |
2400 |
2400 |
2400 |
| Height (mm) |
780 |
780 |
920 |
920 |
1000 |
1000 |
1250 |
1000 |
1250 |
1250 |
| Width (mm) |
770 |
770 |
820 |
820 |
1020 |
1020 |
1250 |
1040 |
1040 |
1040 |
| Weight |
118kg |
126kg |
130kg |
150kg |
260kg |
280kg |
490kg |
640kg |
720kg |
850kg |
* All units can be manufactured to operate at 60Hz and 230 or 480volts
Capacities will be approximately 30% Higher
|